Branch
Line or off-nominal transformer between two buses.
Model Parameters
Symbol |
Units |
Data |
Description |
Typical Value |
Note |
|---|---|---|---|---|---|
\(R\) |
[p.u.] |
|
Series resistance |
Default 0 |
|
\(X\) |
[p.u.] |
|
Series reactance |
Default 0 |
|
\(G\) |
[p.u.] |
|
Total line shunt conductance, split between the ports |
Default 0 |
|
\(B\) |
[p.u.] |
|
Total line shunt susceptance, split between the ports |
Default 0 |
|
\(G_\mathrm{mag}\) |
[p.u.] |
|
Magnetizing shunt conductance at bus 1 |
Default 0 |
|
\(B_\mathrm{mag}\) |
[p.u.] |
|
Magnetizing shunt susceptance at bus 1 |
Default 0 |
|
\(\tau\) |
[p.u.] |
|
Off-nominal tap magnitude on the bus-1 side |
Default 1 |
|
\(\theta\) |
[rad] |
|
Phase-shift angle |
Default 0 |
|
\(S^{\max}\) |
[p.u.] |
|
Apparent power limit at each port |
Default unbounded |
|
\(u\) |
[-] |
|
Service status |
Default true |
Parameter Validation
\(R^2 + X^2 > 0\)
\(\tau > 0\)
\(S^{\max} > 0\)
Model Derived Parameters
Model Ports
Name |
Port |
Description |
|---|---|---|
|
Bus |
Bus-1 port, the tapped side |
|
Bus |
Bus-2 port |
Model Variables
Internal Variables
None.
External Variables
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(V_{\mathrm{r}1}\) |
[p.u.] |
Bus-1 real voltage |
Owned by bus 1 |
\(V_{\mathrm{i}1}\) |
[p.u.] |
Bus-1 imaginary voltage |
Owned by bus 1 |
\(V_{\mathrm{r}2}\) |
[p.u.] |
Bus-2 real voltage |
Owned by bus 2 |
\(V_{\mathrm{i}2}\) |
[p.u.] |
Bus-2 imaginary voltage |
Owned by bus 2 |
Model Equations
Objective
None.
Internal Constraints
Equality
None.
Inequality
With a finite rating \(S^{\max}\):
External Constraints
Power into each bus, added to its balance:
Initialization
None.